PowerNet-MIB DEFINITIONS ::= BEGIN
IMPORTS
enterprises, IpAddress, Gauge, TimeTicks FROM RFC1155-SMI
DisplayString FROM RFC1213-MIB
OBJECT-TYPE FROM RFC-1212
TRAP-TYPE FROM RFC-1215;
apc OBJECT IDENTIFIER ::= { enterprises 318 }
products OBJECT IDENTIFIER ::= { apc 1 }
apcmgmt OBJECT IDENTIFIER ::= { apc 2 }
hardware OBJECT IDENTIFIER ::= { products 1 }
software OBJECT IDENTIFIER ::= { products 2 }
system OBJECT IDENTIFIER ::= { products 3 }
mconfig OBJECT IDENTIFIER ::= { apcmgmt 1 }
mcontrol OBJECT IDENTIFIER ::= { apcmgmt 2 }
ups OBJECT IDENTIFIER ::= { hardware 1 }
measureUps OBJECT IDENTIFIER ::= { hardware 2 }
miniSNMPadapter OBJECT IDENTIFIER ::= { hardware 3 }
powerNetSubAgent OBJECT IDENTIFIER ::= { software 1 }
powerNetSoftwareSystem OBJECT IDENTIFIER ::= { powerNetSubAgent 1 }
powerNetSoftwareConfig OBJECT IDENTIFIER ::= { powerNetSubAgent 2 }
backUPS OBJECT IDENTIFIER ::= { system 1 }
smartUPS OBJECT IDENTIFIER ::= { system 2 }
matrixUPS OBJECT IDENTIFIER ::= { system 3 }
smartUPS250 OBJECT IDENTIFIER ::= { smartUPS 1 }
smartUPS400 OBJECT IDENTIFIER ::= { smartUPS 2 }
smartUPS600 OBJECT IDENTIFIER ::= { smartUPS 3 }
smartUPS900 OBJECT IDENTIFIER ::= { smartUPS 4 }
smartUPS1250 OBJECT IDENTIFIER ::= { smartUPS 5 }
smartUPS2000 OBJECT IDENTIFIER ::= { smartUPS 6 }
smartUPS450 OBJECT IDENTIFIER ::= { smartUPS 7 }
smartUPS700 OBJECT IDENTIFIER ::= { smartUPS 8 }
smartUPS1000 OBJECT IDENTIFIER ::= { smartUPS 9 }
smartUPS1400 OBJECT IDENTIFIER ::= { smartUPS 10 }
smartUPS2200 OBJECT IDENTIFIER ::= { smartUPS 11 }
smartUPS3000 OBJECT IDENTIFIER ::= { smartUPS 12 }
matrixUPS3000 OBJECT IDENTIFIER ::= { matrixUPS 1 }
matrixUPS5000 OBJECT IDENTIFIER ::= { matrixUPS 2 }
upsIdent OBJECT IDENTIFIER ::= { ups 1 }
upsBattery OBJECT IDENTIFIER ::= { ups 2 }
upsInput OBJECT IDENTIFIER ::= { ups 3 }
upsOutput OBJECT IDENTIFIER ::= { ups 4 }
upsConfig OBJECT IDENTIFIER ::= { ups 5 }
upsControl OBJECT IDENTIFIER ::= { ups 6 }
upsTest OBJECT IDENTIFIER ::= { ups 7 }
upsComm OBJECT IDENTIFIER ::= { ups 8 }
upsBasicIdent OBJECT IDENTIFIER ::= { upsIdent 1 }
upsAdvIdent OBJECT IDENTIFIER ::= { upsIdent 2 }
upsBasicBattery OBJECT IDENTIFIER ::= { upsBattery 1 }
upsAdvBattery OBJECT IDENTIFIER ::= { upsBattery 2 }
upsBasicInput OBJECT IDENTIFIER ::= { upsInput 1 }
upsAdvInput OBJECT IDENTIFIER ::= { upsInput 2 }
upsBasicOutput OBJECT IDENTIFIER ::= { upsOutput 1 }
upsAdvOutput OBJECT IDENTIFIER ::= { upsOutput 2 }
upsBasicConfig OBJECT IDENTIFIER ::= { upsConfig 1 }
upsAdvConfig OBJECT IDENTIFIER ::= { upsConfig 2 }
upsBasicControl OBJECT IDENTIFIER ::= { upsControl 1 }
upsAdvControl OBJECT IDENTIFIER ::= { upsControl 2 }
upsBasicTest OBJECT IDENTIFIER ::= { upsTest 1 }
upsAdvTest OBJECT IDENTIFIER ::= { upsTest 2 }
mUpsEnviron OBJECT IDENTIFIER ::= { measureUps 1 }
mUpsContact OBJECT IDENTIFIER ::= { measureUps 2 }
serialPort OBJECT IDENTIFIER ::= { miniSNMPadapter 1}
serialPort1 OBJECT IDENTIFIER ::= { serialPort 1}
serialPort2 OBJECT IDENTIFIER ::= { serialPort 2}
serialPort2Config OBJECT IDENTIFIER ::= { serialPort2 1}
serialPort2Control OBJECT IDENTIFIER ::= { serialPort2 2}
mconfigNumTrapReceivers OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of managers to send traps to."
::= { mconfig 1 }
mconfigTrapReceiverTable OBJECT-TYPE
SYNTAX SEQUENCE OF MconfigTrapReceiverEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of managers to send traps to. The number of
entries is given by the value of mconfigNumTrapReceivers.
Maximum number of Trap Receivers is four."
::= { mconfig 2 }
mconfigTrapReceiverEntry OBJECT-TYPE
SYNTAX MconfigTrapReceiverEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The managers to send traps to."
INDEX { trapIndex}
::= { mconfigTrapReceiverTable 1 }
MconfigTrapReceiverEntry ::=
SEQUENCE {
trapIndex
INTEGER,
receiverAddr
IpAddress,
communityString
DisplayString,
severity
INTEGER,
acceptThisReceiver
INTEGER,
receiveTrapType
INTEGER
}
trapIndex OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a trap receiver entry."
::= { mconfigTrapReceiverEntry 1 }
receiverAddr OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The IP address of the manager to send a trap to."
::= { mconfigTrapReceiverEntry 2 }
communityString OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The community name to use in the trap when
sent to the manager."
::= { mconfigTrapReceiverEntry 3 }
severity OBJECT-TYPE
SYNTAX INTEGER {
information(1),
warning(2),
severe(3)
}
ACCESS read-only
STATUS obsolete
DESCRIPTION
"The severity threshold of traps to send to the manager.
traps are labeled in severity as informational(1), warning(2),
severe(3). Only traps of equal or greater severity than
this value are sent to the manager."
::= { mconfigTrapReceiverEntry 4 }
acceptThisReceiver OBJECT-TYPE
SYNTAX INTEGER {
yes (1),
no (2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"An entry will become active if yes, and will
be deleted if no."
::= { mconfigTrapReceiverEntry 5 }
receiveTrapType OBJECT-TYPE
SYNTAX INTEGER {
powernet (1),
ietf (2),
both (3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The node in this entry will receive traps defined in APC
PowerNet MIB, if this OID is set to yes."
::= { mconfigTrapReceiverEntry 6 }
mconfigBOOTPEnabled OBJECT-TYPE
SYNTAX INTEGER {
yes (1),
no (2)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The value of yes(1) indicates the PowerNet Adapter is configured to
obtain its IP configuration parameters from a BOOTP server.
The value of no(2) indicates adapter will assume IP configuration parameters
values saved in adapter's eeprom, which was orginially configured at local
console."
::= { mconfig 3 }
mconfigTFTPServerIP OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The IP address of TFTP server. If mconfigBOOTPEnabled is yes(1), then this IP address
is provided by BOOTP server and not allowed to be modified; otherwise, this IP address
can be modified.
Before using TFTP to load new code image, the image file should be placed in proper
directory of the specified TFTP server."
::= { mconfig 4 }
newCodeAuthentViaTFTP OBJECT-TYPE
SYNTAX INTEGER {
unknown (1),
validNewAgentCodeImage (2),
sameAgentCodeImage (3),
invalidAgentCodeImage (4)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Once mcontrolRestartAgent is set to loadAndExecuteNewAgent (3), PowerNet adapter will
start to load the remote image file, for authentication only, instead of saving the code
into flash memory. Only if a validNewAgentCodeImage (1) is found will the agent reboot
the PowerNet adaoter and invoke the loader to load and save new code into the flash memory.
Otherwise, the current agent code will continue to run.
This OID shows the result of the above authentication process.
validNewAgentCodeImage (1) means the code image on TFTP server
is a valid APC agent code and is different version from the current agent.
Once agent identifies this, loader will start to update flash memory with
the new agent code.
sameAgentCodeImage (2) means the code image on TFTP server is exactly the
same as the currently running agent. Currently running agent will not invoke
loader to load the same again.
invalidAgentCodeImage (3) means the code image on TFTP server is NOT a valid
APC agent code. Thus, current agent will not load it into the flash memory.
The value of this OID will be associated with TRAP codeImageAuthentDone."
::= { mconfig 5 }
mcontrolRestartAgent OBJECT-TYPE
SYNTAX INTEGER {
restartCurrentAgent (1),
continueCurrentAgent (2),
loadAndExecuteNewAgent (3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting this OID to restartCurrentAgent (1)
will restart the same SNMP agent code currently saved in
flash memory.
Setting this OID to loadAndExecuteNewAgent (3) will enable adapter
to load a new agent code into the flash memory and start to
execute this new agent code. Bootp/tftp is the default protocol."
::= { mcontrol 1 }
powerNetSoftwareSystemDescription OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..79))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"A brief description of the PowerNet sub-agent."
::= { powerNetSoftwareSystem 1 }
powerNetSoftwareOid OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The object identifier of the PowerNet sub-agent."
::= { powerNetSoftwareSystem 2 }
powerNetSmuxPeer OBJECT IDENTIFIER ::= { powerNetSoftwareOid 1 }
powerNetDPIPeer OBJECT IDENTIFIER ::= { powerNetSoftwareOid 2 }
powerNetSoftwareSystemUpTime OBJECT-TYPE
SYNTAX TimeTicks
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The time that the sub-agent has been running."
::= { powerNetSoftwareSystem 3 }
powerNetSoftwareTableSize OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of software modules supporting the UPS."
::= { powerNetSoftwareConfig 1 }
powerNetSoftwareTable OBJECT-TYPE
SYNTAX SEQUENCE OF SoftwareEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of the software monitoring the UPS."
::= { powerNetSoftwareConfig 2 }
powerNetSoftwareEntry OBJECT-TYPE
SYNTAX SoftwareEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"An entry containing information on a software module."
INDEX { moduleNumber }
::= { powerNetSoftwareTable 1 }
SoftwareEntry ::=
SEQUENCE {
moduleNumber
INTEGER,
moduleName
DisplayString,
moduleVersion
DisplayString,
moduleDate
DisplayString
}
moduleNumber OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index into the Software Entry Table"
::= { powerNetSoftwareEntry 1 }
moduleName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..79))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The name of the software module."
::= { powerNetSoftwareEntry 2 }
moduleVersion OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..8))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The version of the software module."
::= { powerNetSoftwareEntry 3 }
moduleDate OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..9))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The date of the software module represented as mm-dd-yy."
::= { powerNetSoftwareEntry 4 }
upsBasicIdentModel OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The UPS model name (e.g. 'APC Smart-UPS 600')."
::= { upsBasicIdent 1 }
upsBasicIdentName OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-write
STATUS mandatory
DESCRIPTION
"An 8 byte ID string identifying the UPS. This object
can be set by the administrator."
::= { upsBasicIdent 2 }
upsAdvIdentFirmwareRevision OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The firmware revision of the UPS system's microprocessor."
::= { upsAdvIdent 1 }
upsAdvIdentDateOfManufacture OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The date when the UPS was manufactured in mm/dd/yy format."
::= { upsAdvIdent 2 }
upsAdvIdentSerialNumber OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"An 8-character string identifying the serial number of
the UPS internal microprocessor. This number is set at
the factory. NOTE: This number does NOT correspond to
the serial number on the rear of the UPS."
::= { upsAdvIdent 3 }
upsBasicBatteryStatus OBJECT-TYPE
SYNTAX INTEGER {
unknown(1),
batteryNormal(2),
batteryLow(3)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The status of the UPS batteries. A batteryLow(3)
value indicates the UPS will be unable to sustain the
current load, and its services will be lost if power is
not restored. The amount of run time in reserve at the
time of low battery can be configured by the
upsAdvConfigLowBatteryRunTime."
::= { upsBasicBattery 1 }
upsBasicBatteryTimeOnBattery OBJECT-TYPE
SYNTAX TimeTicks
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The elapsed time since the UPS has switched to battery
power."
::= { upsBasicBattery 2 }
upsBasicBatteryLastReplaceDate OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The date when the UPS system's batteries were last replaced
in mm/dd/yy format. For Smart-UPS models, this value
is originally set in the factory. When the UPS batteries
are replaced, this value should be reset by the administrator."
::= { upsBasicBattery 3 }
upsAdvBatteryCapacity OBJECT-TYPE
SYNTAX Gauge
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The remaining battery capacity expressed in
percent of full capacity."
::= { upsAdvBattery 1 }
upsAdvBatteryTemperature OBJECT-TYPE
SYNTAX Gauge
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The current internal UPS temperature expressed in
Celsius."
::= { upsAdvBattery 2 }
upsAdvBatteryRunTimeRemaining OBJECT-TYPE
SYNTAX TimeTicks
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The UPS battery run time remaining before battery
exhaustion."
::= { upsAdvBattery 3 }
upsAdvBatteryReplaceIndicator OBJECT-TYPE
SYNTAX INTEGER {
noBatteryNeedsReplacing(1),
batteryNeedsReplacing(2)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicates whether the UPS batteries need replacing."
::= { upsAdvBattery 4 }
upsAdvBatteryNumOfBattPacks OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of external battery packs connected to the UPS. If
the UPS does not use smart cells then the agent reports
ERROR_NO_SUCH_NAME."
::= { upsAdvBattery 5 }
upsAdvBatteryNumOfBadBattPacks OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of external battery packs connected to the UPS that
are defective. If the UPS does not use smart cells then the
agent reports ERROR_NO_SUCH_NAME."
::= { upsAdvBattery 6 }
upsBasicInputPhase OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The current AC input phase."
::= { upsBasicInput 1 }
upsAdvInputLineVoltage OBJECT-TYPE
SYNTAX Gauge
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The current utility line voltage in VAC."
::= { upsAdvInput 1 }
upsAdvInputMaxLineVoltage OBJECT-TYPE
SYNTAX Gauge
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The maximum utility line voltage in VAC over the
previous 1 minute period."
::= { upsAdvInput 2 }
upsAdvInputMinLineVoltage OBJECT-TYPE
SYNTAX Gauge
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The minimum utility line voltage in VAC over the
previous 1 minute period."
::= { upsAdvInput 3 }
upsAdvInputFrequency OBJECT-TYPE
SYNTAX Gauge
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The current input frequency to the UPS system in Hz."
::= { upsAdvInput 4 }
upsAdvInputLineFailCause OBJECT-TYPE
SYNTAX INTEGER {
noTransfer(1),
highLineVoltage(2),
brownout(3),
blackout(4),
smallMomentarySag(5),
deepMomentarySag(6),
smallMomentarySpike(7),
largeMomentarySpike(8)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The reason for the occurrence of the last transfer to UPS
battery power. The variable is set to:
- noTransfer(1) -- if there is no transfer yet.
- highLineVoltage(2) -- if the transfer to battery is caused
by an over voltage greater than the high transfer vloltage.
- brownout(3) -- if the duration of the outage is greater than
five seconds and the line voltage is between 40% of the
rated output voltage and the low transfer voltage.
- blackout(4) -- if the duration of the outage is greater than five
seconds and the line voltage is between 40% of the rated
output voltage and ground.
- smallMomentarySag(5) -- if the duration of the outage is less
than five seconds and the line voltage is between 40% of the
rated output voltage and the low transfer voltage.
- deepMomentarySag(6) -- if the duration of the outage is less
than five seconds and the line voltage is between 40% of the
rated output voltage and ground. The variable is set to
- smallMomentarySpike(7) -- if the line failure is caused by a
rate of change of input voltage less than ten volts per cycle.
- largeMomentarySpike(8) -- if the line failure is caused by
a rate of change of input voltage greater than ten volts per cycle."
::= { upsAdvInput 5 }
upsBasicOutputStatus OBJECT-TYPE
SYNTAX INTEGER {
unknown(1),
onLine(2),
onBattery(3),
onSmartBoost(4),
timedSleeping(5),
softwareBypass(6),
off(7),
rebooting(8),
switchedBypass(9),
hardwareFailureBypass(10),
sleepingUntilPowerReturn(11),
onSmartTrim(12)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The current state of the UPS. If the UPS is unable
to determine the state of the UPS this variable is set
to unknown(1)."
::= { upsBasicOutput 1 }
upsBasicOutputPhase OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The current output phase."
::= { upsBasicOutput 2 }
upsAdvOutputVoltage OBJECT-TYPE
SYNTAX Gauge
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The output voltage of the UPS system in VAC."
::= { upsAdvOutput 1 }
upsAdvOutputFrequency OBJECT-TYPE
SYNTAX Gauge
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The current output frequency of the UPS system in Hz."
::= { upsAdvOutput 2 }
upsAdvOutputLoad OBJECT-TYPE
SYNTAX Gauge
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The current UPS load expressed in percent
of rated capacity."
::= { upsAdvOutput 3 }
upsAdvOutputCurrent OBJECT-TYPE
SYNTAX Gauge
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The current in ampres drawn by the load on the UPS."
::= { upsAdvOutput 4 }
upsBasicConfigNumDevices OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of devices that are plugged into the UPS."
::= { upsBasicConfig 1 }
upsBasicConfigDeviceTable OBJECT-TYPE
SYNTAX SEQUENCE OF UpsBasicConfigDeviceEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of devices that are plugged into the UPS.
The number of entries is given by the value of
upsBasicConfigNumDevices."
::= { upsBasicConfig 2 }
upsBasicConfigDeviceEntry OBJECT-TYPE
SYNTAX UpsBasicConfigDeviceEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The devices plugged in to the UPS."
INDEX { deviceIndex }
::= { upsBasicConfigDeviceTable 1 }
UpsBasicConfigDeviceEntry ::=
SEQUENCE {
deviceIndex
INTEGER,
deviceName
DisplayString,
vaRating
INTEGER,
acceptThisDevice
INTEGER
}
deviceIndex OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index of the device that is plugged into the UPS."
::= { upsBasicConfigDeviceEntry 1 }
deviceName OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The name/description of the device plugged into the UPS."
::= { upsBasicConfigDeviceEntry 2 }
vaRating OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The volt-amp rating of the device plugged into the UPS."
::= { upsBasicConfigDeviceEntry 3 }
acceptThisDevice OBJECT-TYPE
SYNTAX INTEGER {
yes(1),
no(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"An entry is added if yes, the entry is deleted if no."
::= { upsBasicConfigDeviceEntry 4 }
upsAdvConfigRatedOutputVoltage OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The nominal output voltage from the UPS in VAC.
Possible values are 100, 120, 208, 220, 225, 230 and 240.
NOTE: Only units that are 220, 225, 230 and 240 can be
changed. Allowable set values are 220, 225, 230, and 240.
For these adjustable units, if a value other than
a supported value is provided in a set request, the
UPS interprets it as the next lower acceptable value.
If the provided value is lower than the lowest acceptable
value, the lowest acceptable value is used."
::= { upsAdvConfig 1 }
upsAdvConfigHighTransferVolt OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The maximum line voltage in VAC allowed before the
UPS system transfers to battery backup.
Allowed values depend on the UPS used:
100 volt units allow settings of 108, 110, 112, and 114.
120 volt units allow settings of 129, 132, 135, and 138.
208 volt units allow settings of 224, 229, 234, and 239.
230 volt units allow settings of 253, 264, 271, and 280.
Matrix Notes:
Matrix units configured for 208V input allow settings of
240, 244, 248, and 252. Matrix units configured for 240V
input allow settings of 276, 264, 253, and 282.
If a value other than a supported value is provided in a
set request, the UPS interprets it as the next lower
acceptable value. If the provided value is lower than
the lowest acceptable value, the lowest acceptable
value is used."
::= { upsAdvConfig 2 }
upsAdvConfigLowTransferVolt OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The minimum line voltage in VAC allowed before the
UPS system transfers to battery backup.
Allowable values depend on the UPS used:
100 volt units allow settings of 81, 83, 85, 87.
120 volt units allow settings of 97, 100, 103, 106.
208 volt units allow settings of 168, 172, 177, 182.
230 volt units allow settings of 188, 196, 204, 208.
Matrix Notes:
Matrix units configured for 208V input have a fixed low
transfer voltage of 156 volts.
Matrix units configured for 240V input have a fixed low
transfer voltage of 180 volts.
If a value other than a supported value is provided in a
set request, the UPS interprets it as a the next higher
acceptable value. If the provided value is higher than
the highest acceptable value, the highest acceptable
value is used."
::= { upsAdvConfig 3 }
upsAdvConfigAlarm OBJECT-TYPE
SYNTAX INTEGER {
timed(1),
atLowBattery(2),
never(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A flag indicating how the UPS should handle audible
line fail alarms."
::= { upsAdvConfig 4 }
upsAdvConfigAlarmTimer OBJECT-TYPE
SYNTAX TimeTicks
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The time after initial line failure at which the UPS
begins emitting audible alarms (beeping). This timer is
observerd only if the value of extControlAlarm is timed(2).
Allowed values are 0 or 30 seconds.
If a value other than a supported value is provided in a
set request, the UPS interprets it as a the next lower
acceptable value. If the provided value is lower than
the lowest acceptable value, the lowest acceptable
value is used."
::= { upsAdvConfig 5 }
upsAdvConfigMinReturnCapacity OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The minimum battery capacity required before the UPS will
return from a low battery shutdown condition. The capacity is
measured from 0% battery capacity (or Low Battery) as a percent
of full capacity (100%). In other words, the UPS will not re-energize
the output until the battery has charged so that its' capacity is equal
to this value. Allowed values are 0, 10, 25, or 90 percent.
If a value other than a supported value is provided in a
set request, the UPS interprets the value as the next higher
acceptable value. If the provided value is higher than
the highest acceptable value, the highest acceptable
value (90%) is used."
::= { upsAdvConfig 6 }
upsAdvConfigSensitivity OBJECT-TYPE
SYNTAX INTEGER {
auto(1),
low(2),
medium(3),
high(4)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The sensitivity of the UPS to utility line abnormalities
or noises."
::= { upsAdvConfig 7 }
upsAdvConfigLowBatteryRunTime OBJECT-TYPE
SYNTAX TimeTicks
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The desired run time of the UPS, in seconds, once the
low battery condition is reached. Allowed values are 120,
300, 420, or 600 seconds. During this time the UPS will
produce a constant warning tone which can not be disabled.
If a value other than a supported value is provided in a set
request, the UPS interprets the value as the next higher
acceptable value. If the provided value is higher than the
highest acceptable value, the highest acceptable value is used."
::= { upsAdvConfig 8 }
upsAdvConfigReturnDelay OBJECT-TYPE
SYNTAX TimeTicks
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The delay in seconds after utility line power returns
before the UPS will turn on. This value is also used
when the UPS comes out of a reboot and before the UPS
wakes up from 'sleep' mode. Allowed values are 0, 60,
180 and 300 seconds.
If a value other than a supported value is provided in a
set request, the UPS interprets it as a the next higher
acceptable value. If the provided value is higher than
the highest acceptable value, the highest acceptable
value is used."
::= { upsAdvConfig 9 }
upsAdvConfigShutoffDelay OBJECT-TYPE
SYNTAX TimeTicks
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The delay in seconds the UPS remains on after being told
to turn off. Allowed values are 20, 180, 300, and
600 seconds.
If a value other than a supported value is provided in a
set request, the UPS interprets it as a the next higher
acceptable value. If the provided value is higher than
the highest acceptable value, the highest acceptable
value is used."
::= { upsAdvConfig 10 }
upsAdvConfigUpsSleepTime OBJECT-TYPE
SYNTAX TimeTicks
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The time in seconds for the UPS to go to 'sleep' when
instructed. When in sleep mode, the UPS will not provide
output power regardless of the input line state. Once the
specified time has elapsed, output power will be restored.
This is a configuration setting. The UPS will not go to
sleep until told to do so by the manager from a management
station.
Any input value is allowed, however the UPS only recognizes
1/10 of an hour increments. The provided value will be
rounded to the closest 1/10 of an hour with one exception:
Any value entered between 1 and 540 seconds will be rounded
to 360 seconds (or 6 minutes)."
::= { upsAdvConfig 11 }
upsAdvConfigSetEEPROMDefaults OBJECT-TYPE
SYNTAX INTEGER {
noSetEEPROMDefaults(1),
setEEPROMDefaults(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"WRITE: Resets the UPS EEPROM variables to default values.
READ: returns 0"
::= { upsAdvConfig 12 }
upsAdvConfigDipSwitchSetting OBJECT-TYPE
SYNTAX SEQUENCE OF UpsAdvConfigDipSwitchEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Current settings of UPS dip switches."
::= { upsAdvConfig 13 }
upsAdvConfigDipSwitchEntry OBJECT-TYPE
SYNTAX UpsAdvConfigDipSwitchEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The current setting of one dip switch."
INDEX { dipSwitchIndex }
::= { upsAdvConfigDipSwitchSetting 1 }
UpsAdvConfigDipSwitchEntry ::=
SEQUENCE {
dipSwitchIndex
INTEGER,
dipSwitchStatus
INTEGER
}
dipSwitchIndex OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index of a UPS dip switch."
::= { upsAdvConfigDipSwitchEntry 1 }
dipSwitchStatus OBJECT-TYPE
SYNTAX INTEGER {
on(1),
off(2)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The setting of a UPS dip switch."
::= { upsAdvConfigDipSwitchEntry 2 }
upsAdvConfigBattExhaustThresh OBJECT-TYPE
SYNTAX TimeTicks
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The number of seconds prior to battery exhaustion when the
UPS will switch off power to it's load."
::= { upsAdvConfig 14 }
upsAdvConfigPassword OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The password entered at the UPS front panel to enable local
configuation of the EEProm. If the password is disabled or
is not supported, then the agent returns a null string."
::= { upsAdvConfig 15 }
upsAdvConfigAllowedSetTable OBJECT-TYPE
SYNTAX SEQUENCE OF ApcUpsConfigEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The table listing the allowed values for all discrete
configurable UPS variables."
::= { upsAdvConfig 16 }
apcUpsConfigEntry OBJECT-TYPE
SYNTAX ApcUpsConfigEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The table entry for a configurable UPS variable."
INDEX { apcUpsConfigFieldIndex }
::= { upsAdvConfigAllowedSetTable 1 }
ApcUpsConfigEntry ::= SEQUENCE {
apcUpsConfigFieldIndex INTEGER,
apcUpsConfigFieldOID OBJECT IDENTIFIER,
apcUpsConfigFieldValueRange DisplayString
}
apcUpsConfigFieldIndex OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to an eeprom field entry."
::= { apcUpsConfigEntry 1 }
apcUpsConfigFieldOID OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The OID of the current configurable value."
::= { apcUpsConfigEntry 2 }
apcUpsConfigFieldValueRange OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The distcrete set of allowed values of a configurable
register. Individual values are delimited by a comma."
::= { apcUpsConfigEntry 3 }
upsBasicControlConserveBattery OBJECT-TYPE
SYNTAX INTEGER {
noTurnOffUps(1),
turnOffUpsToConserveBattery(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting this variable to turnUpsOffToConserveBattery(2)
causes a UPS on battery to be put into 'sleep' mode. The
UPS will turn back on when utility power is restored.
Attempting to turn off a UPS that is not on battery will
result in a badValue error.
Setting this value to noTurnOffUps(1) has no
effect.
The value noTurnOffUps(1) will always be returned
when the variable is read."
::= { upsBasicControl 1 }
upsAdvControlUpsOff OBJECT-TYPE
SYNTAX INTEGER {
noTurnUpsOff(1),
turnUpsOff(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting this variable to turnUpsOff(2) causes
the UPS to shut off. When in this state, the UPS
will not provide output power regardless of the input
line state. The ON/OFF switch on the UPS
must be toggled for the UPS to return to operation.
Setting this value to noTurnUpsOff(1) has no
effect.
The value noTurnUpsOff(1) will always be returned
when the variable is read."
::= { upsAdvControl 1 }
upsAdvControlRebootUps OBJECT-TYPE
SYNTAX INTEGER {
noRebootUps(1),
rebootUps(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting this variable to rebootUps(2) causes the
UPS to shut off and turn back on.
Setting this value to noRebootUps(1) has no effect.
The value noRebootUps(1) will always be returned
when the variable is read."
::= { upsAdvControl 2 }
upsAdvControlUpsSleep OBJECT-TYPE
SYNTAX INTEGER {
noPutUpsToSleep(1),
putUpsToSleep(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting this variable to putUpsToSleep(2) causes
the UPS to go to sleep for the time specified by
upsAdvConfigUpsSleepTime.
When in sleep mode, the UPS will not provide output
power regardless of the input line state. Once the
specified time has elapsed, output power will be
restored.
Setting this value to noPutUpsToSleep(1) has no
effect.
The value noPutUpsToSleep(1) will always be returned
when the variable is read."
::= { upsAdvControl 3 }
upsAdvControlSimulatePowerFail OBJECT-TYPE
SYNTAX INTEGER {
noSimulatePowerFailure(1),
simulatePowerFailure(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting this variable to simulatePowerFailure(2) causes
the UPS switch to battery power.
Setting this value to noSimulatePowerFailure(1) has no
effect.
The value noSimulatePowerFailure(1) will always be returned
when the variable is read."
::= { upsAdvControl 4 }
upsAdvControlFlashAndBeep OBJECT-TYPE
SYNTAX INTEGER {
noFlashAndBeep(1),
flashAndBeep(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting this variable to flashAndBeep(2) causes the
UPS to beep and simultaneously turn on the UPS front
panel lights (Smart-UPS only).
Setting this value to noFlashAndBeep(1) has no
effect.
The value noFlashAndBeep(1) will always be returned
when the variable is read."
::= { upsAdvControl 5 }
upsAdvControlTurnOnUPS OBJECT-TYPE
SYNTAX INTEGER {
noTurnOnUPS(1),
turnOnUPS(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting this variable to turnOnUPS(2) causes the
UPS to be turned on immediately, provided
upsBasicOutputStatus does not read ON.
Setting this value to noTurnOnUPS(1) has no
effect.
The value noTurnOnUPS(1) will always be returned
when the variable is read.
This action is only available with the APC
Mini-SNMP Adapter."
::= { upsAdvControl 6 }
upsAdvControlBypassSwitch OBJECT-TYPE
SYNTAX INTEGER {
noBypassSwitch (1),
switchToBypass (2),
switchOutOfBypass(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"This switch pertains to the Matrix UPS. It switchs the
UPS in or out of bypass mode."
::= { upsAdvControl 7 }
upsAdvTestDiagnosticSchedule OBJECT-TYPE
SYNTAX INTEGER {
unknown(1),
biweekly(2),
weekly(3),
atTurnOn(4),
never(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The UPS system's automatic battery test schedule."
::= { upsAdvTest 1 }
upsAdvTestDiagnostics OBJECT-TYPE
SYNTAX INTEGER {
noTestDiagnostics(1),
testDiagnostics(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting this variable to testDiagnostics(2) causes
the UPS to perform a diagnostic self test.
Setting this value to noTestDiagnostics(1) has no
effect.
The value noTestDiagnostics(1) will always be returned
when the variable is read."
::= { upsAdvTest 2 }
upsAdvTestDiagnosticsResults OBJECT-TYPE
SYNTAX INTEGER {
ok(1),
failed(2),
invalidTest(3),
testInProgress(4)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The results of the last UPS diagnostics test performed."
::= { upsAdvTest 3 }
upsAdvTestLastDiagnosticsDate OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The date the last UPS diagnostics test was performed in
mm/dd/yy format."
::= { upsAdvTest 4 }
upsAdvTestRuntimeCalibration OBJECT-TYPE
SYNTAX INTEGER {
noPerformCalibration(1),
performCalibration(2),
cancelCurrentCalibration(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting this variable to performCalibration(2) causes
the UPS to discharge to calibrate the UPS.
The test will only start if the battery capacity is 100%.
The test runs until capacity is less than 25%.
Setting this variable to cancelCurrentCalibration(3)
after setting performCalibration(2) will cancel the
current discharge.
Setting this variable to noPerformCalibration(1)
will have no effect.
The value noPerformCalibration(1) will always be returned
when the variable is read.
The result of the calibration will be saved in
upsAdvTestCalibrationResult."
::= { upsAdvTest 5 }
upsAdvTestCalibrationResults OBJECT-TYPE
SYNTAX INTEGER {
ok(1),
invalidCalibration(2),
calibrationInProgress(3)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The results of the last runtime calibration.
Value ok(1) means a successful runtime calibration.
Value invalidCalibration(2) indicates last calibration did
not take place since the battery capacity was below
100%.
Value calibrationInProgress(3) means a calibration
is occurring now. "
::= { upsAdvTest 6 }
upsAdvTestCalibrationDate OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The date the last UPS runtime calibration was
performed in mm/dd/yy format."
::= { upsAdvTest 7 }
upsCommStatus OBJECT-TYPE
SYNTAX INTEGER {
ok(1),
noComm(2)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The status of agent's communication with UPS. "
::= { upsComm 1 }
mUpsEnvironAmbientTemperature OBJECT-TYPE
SYNTAX Gauge
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The ambient temperature in Celsius."
::= { mUpsEnviron 1 }
mUpsEnvironRelativeHumidity OBJECT-TYPE
SYNTAX Gauge
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The relative humidity as a percentage."
::= { mUpsEnviron 2 }
mUpsContactNumContacts OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of contacts supported by the Measure-UPS."
::= { mUpsContact 1 }
mUpsContactTable OBJECT-TYPE
SYNTAX SEQUENCE OF ContactEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of contacts supported by the Measure-UPS."
::= { mUpsContact 2 }
mUpsContactEntry OBJECT-TYPE
SYNTAX ContactEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A contact entry containing information for a given contact."
INDEX { contactNumber }
::= { mUpsContactTable 1 }
ContactEntry ::=
SEQUENCE {
contactNumber
INTEGER,
normalState
INTEGER,
description
DisplayString,
monitoringStatus
INTEGER,
currentStatus
INTEGER
}
contactNumber OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"An index identifying the contact on the Measure-UPS."
::= { mUpsContactEntry 1 }
normalState OBJECT-TYPE
SYNTAX INTEGER {
unknown(1),
open(2),
closed(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The normal operating position of the contact. If the normal
operating postion cannot be set then it is contolled via the
dip switch on the Measure-UPS and is therefore read-only."
::= { mUpsContactEntry 2 }
description OBJECT-TYPE
SYNTAX DisplayString
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The decsription of the purpose/use of the contact."
::= { mUpsContactEntry 3 }
monitoringStatus OBJECT-TYPE
SYNTAX INTEGER {
unknown(1),
enabled(2),
disabled(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A flag indicating whether this contact is
monitored, or not."
::= { mUpsContactEntry 4 }
currentStatus OBJECT-TYPE
SYNTAX INTEGER {
unknown(1),
noFault(2),
fault(3)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"This value indicates the current state of the contact.
If the contact is not in its normal state. This value
is set to fault(2)."
::= { mUpsContactEntry 5 }
serialPort2Mode OBJECT-TYPE
SYNTAX INTEGER {
localConsole(1),
passthrough(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting this variable to passthrough will enable mini's port2
behave like a UPS port. Choosing localConsole will enable the port
to be used as local console."
::= { serialPort2Config 1 }
setPulseOnTXD OBJECT-TYPE
SYNTAX INTEGER {
noSetPulseOnTXD(1),
setPulseOnTXD(2),
setTXDLow(3),
setTXDHigh(4)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting this variable to setPulseOnTXD(2)
causes adapter to generate a PULSE on TXD pin of serial port 2.
The duration in the prototype implementation will be 1 second.
Setting this value to noSetPulseOnTXD(1) has no
effect.
The value noSetPulseOnTXD(1) will always be returned
when the variable is read.
Setting this value to setTXDLow(3), or setTXDHigh(4) will keep TXD
always low or high respectively."
::= { serialPort2Control 1 }
communicationLost TRAP-TYPE
ENTERPRISE apc
DESCRIPTION
"SEVERE: Communication to the UPS has been lost. Steps
to reestablish communication are in progress."
::= 1
upsOverload TRAP-TYPE
ENTERPRISE apc
DESCRIPTION
"SEVERE: The UPS has sensed a load greater than 100 percent
of its rated capacity."
::= 2
upsDiagnosticsFailed TRAP-TYPE
ENTERPRISE apc
DESCRIPTION
"SEVERE: The UPS failed its internal diagnostic self-test."
::= 3
upsDischarged TRAP-TYPE
ENTERPRISE apc
DESCRIPTION
"SEVERE: The UPS batteries are discharged; if utility power fails
an immediate low battery condition will exist. Sufficient runtime
for necessary action cannot be guaranteed."
::= 4
upsOnBattery TRAP-TYPE
ENTERPRISE apc
DESCRIPTION
"WARNING: The UPS has switched to battery backup power."
::= 5
smartBoostOn TRAP-TYPE
ENTERPRISE apc
DESCRIPTION
"WARNING: The UPS has enabled SmartBoost."
::= 6
lowBattery TRAP-TYPE
ENTERPRISE apc
DESCRIPTION
"SEVERE: The UPS batteries are low and will soon be exhausted.
If utility power is not restored the UPS will put itself
to 'sleep' and immediately cut power to the load."
::= 7
communicationEstablished TRAP-TYPE
ENTERPRISE apc
DESCRIPTION
"INFORMATION: Communication with the UPS has been established."
::= 8
powerRestored TRAP-TYPE
ENTERPRISE apc
DESCRIPTION
"INFORMATION: Utility power has been restored."
::= 9
upsDiagnosticsPassed TRAP-TYPE
ENTERPRISE apc
DESCRIPTION
"INFORMATION: The UPS passed its internal self-test."
::= 10
returnFromLowBattery TRAP-TYPE
ENTERPRISE apc
DESCRIPTION
"INFORMATION: The UPS has returned from a low battery
condition."
::= 11
upsTurnedOff TRAP-TYPE
ENTERPRISE apc
DESCRIPTION
"WARNING: The UPS has been turned 'off' by the management station."
::= 12
upsSleeping TRAP-TYPE
ENTERPRISE apc
DESCRIPTION
"WARNING: The UPS is entering 'sleep' mode. Power
to the load will be cut off."
::= 13
upsWokeUp TRAP-TYPE
ENTERPRISE apc
DESCRIPTION
"INFORMATION: The UPS has returned from 'sleep' mode. Power
to the load has been restored."
::= 14
upsRebootStarted TRAP-TYPE
ENTERPRISE apc
DESCRIPTION
"WARNING: The UPS has started its reboot sequence.
The UPS will reboot itself at this time."
::= 15
upsDipSwitchChanged TRAP-TYPE
ENTERPRISE apc
DESCRIPTION
"WARNING: The dip switch settings on the UPS have been
changed, possibly altering UPS performance."
::= 16
upsBatteryNeedsReplacement TRAP-TYPE
ENTERPRISE apc
DESCRIPTION
"SEVERE: The batteries of the UPS need immediate replacement."
::= 17
contactFault TRAP-TYPE
ENTERPRISE apc
DESCRIPTION
"SEVERE: One of the contacts on the Measure-UPS has
changed from its default position."
::= 18
contactFaultResolved TRAP-TYPE
ENTERPRISE apc
DESCRIPTION
"INFORMATION: A fault on one of the Measure-UPS contacts
has been resolved."
::= 19
hardwareFailureBypass TRAP-TYPE
ENTERPRISE apc
DESCRIPTION
"SEVERE: UPS on bypass due to hardware failure"
::= 20
softwareBypass TRAP-TYPE
ENTERPRISE apc
DESCRIPTION
"WARNING: UPS on bypass - user set via software or panel"
::= 21
switchedBypass TRAP-TYPE
ENTERPRISE apc
DESCRIPTION
"WARNING: UPS on bypass - user set via rear switch"
::= 22
returnFromBypass TRAP-TYPE
ENTERPRISE apc
DESCRIPTION
"INFORMATIONAL: UPS has returned from bypass"
::= 23
bypassPowerSupplyFailure TRAP-TYPE
ENTERPRISE apc
DESCRIPTION
"SEVERE: Base module bypass power supply needs repair"
::= 24
baseFanFailure TRAP-TYPE
ENTERPRISE apc
DESCRIPTION
"SEVERE: Base module fan needs repair"
::= 25
batteryPackCommLost TRAP-TYPE
ENTERPRISE apc
DESCRIPTION
"SEVERE: Check installation of external battery packs signal cable"
::= 26
batteryPackCommEstablished TRAP-TYPE
ENTERPRISE apc
DESCRIPTION
"INFORMATIONAL: UPS is communicating with the external battery packs."
::= 27
calibrationStart TRAP-TYPE
ENTERPRISE apc
DESCRIPTION
"INFORMATIONAL: A battery calibration test has been initiated on the UPS."
::= 28
restartAgent TRAP-TYPE
ENTERPRISE apc
DESCRIPTION
"INFORMATIONAL: Agent restarting as commanded by manager."
::= 29
upsTurnedOn TRAP-TYPE
ENTERPRISE apc
DESCRIPTION
"INFORMATIONAL: A UPS is turned on."
::= 30
smartAvrReducing TRAP-TYPE
ENTERPRISE apc
DESCRIPTION
"WARNING: The UPS is reducing the line voltage via Smart-AVR."
::= 31
codeAuthenticationDone TRAP-TYPE
ENTERPRISE apc
VARIABLES { mconfigTFTPServerIP, newCodeAuthentViaTFTP }
DESCRIPTION
"INFORMATIONAL: Authentication on agent code image is done."
::= 32
END